STATE BUILDING CODE INTERPRETATION NO. 95-25
 
CODE: 1994 Uniform Building Code (UBC) 
SECTION:  Section 313.8.2.1
QUESTION:  Was it the intention of the requirement in Section 313.8.2.1 to be exclusive; that is, can the "increases" listed from UBC Chapter Five (Sections 505--Area Increases, 506--Building Height Increases, and 508--Fire-Resistive Substitutions) be granted for a building installing an approved automatic sprinkler system to fulfill the requirements of Section 313.8.2.1?
ANSWER:  It is the intent of Section 313.8.2.1 that the provisions of Section 508--Fire-Resistive Substitution not be allowed when an approved automatic sprinkler system is required throughout a building classified as an LC Occupancy and as described in Section 313.8.2.1.  Section 505 or 506 may be used.
SUPERSEDES: None 
REQUESTED BY:  City of Bellingham Fire Dept.