| CODE: | 1992 Washington State Uniform Building Code |
| SECTION: | Section 51-20-3802 (e) 3 |
| QUESTION: | 1.
If three Group E, Division 1 Portable School Classrooms, which exceed 5,
000 square feet in aggregate area, are located with 20 feet spacing between
buildings, does this consititute a "cluster" under Section 51-20-3802 (e)
3?
2. If the answer to the first question is yes, should classrooms in portables existing on the site also be included in the "cluster" and therefore sprinklered? |
| ANSWER: | 1.
No. When the spacing between the portables is 20 or more feet, they are
not considered clusters.
2. No. |
| SUPERSEDES: | None |
| REQUESTED BY: | Yakima County |