CODE: |
2003
IFC / IBC |
|
SECTION: |
2003 IBC Section 3403.1 |
|
QUESTION: |
1. An existing building is being remodeled and
undergoing a change in occupancy to include an A-2 occupancy with an occupant
load of 246. Does this proposed
alteration require sprinklers? 2. If the above answer is yes, would then the
same apply if the present use was a bar and additional space was being added? |
|
ANSWER: |
1. Yes.
The intent of the amendment to IFC Section 903.2.1.2 is to require
sprinklers in occupancies where there is an increased risk to fire and life
safety with the added distractions of alcohol and/or music and entertainment,
and a high occupant density. This amendment was added in view of the tragic
losses in 2. Yes. |
|
SUPERSEDES: |
None |
|
REQUESTED BY: |
SBCC |